completing pump units on the basis of pump ЦНСн 315-378 (Q=315 m3/h, H=375 m).
main line, technological and auxiliary pipe lines. - Preliminary water discharge unit is used to separate water and associated gas from oil;
- Preliminary water discharge unit consists of:

|
№ |
Characteristic |
Data |
|
1 |
Type |
Explosion proof |
|
2 |
Explosion proof |
ExdIIBT4 |
|
3 |
Dimension height ,mm |
450 |
|
4 |
Mounting arrangement |
B3R* |
|
5 |
Output, kW |
500 |
|
6 |
Speed, rpm |
1491 |
|
7 |
Voltage, V |
10 000 |
|
8 |
Rotor direction of rotation (view from coupling side) |
CCW |
|
9 |
Connection scheme |
Star |
|
10 |
Nom no-load current, A |
36.1 |
|
11 |
Frequency, Hz |
50 |
|
12 |
Duty |
S1 |
|
13 |
Insulation |
F |
|
14 |
Degree of protection |
IP55 |
|
15 |
Rotor cage material |
copper |
|
16 |
Ambient temperature,0C: Operation Transport and storage |
-55……+40 -60….+40 |
|
17 |
Noise pressure level, dB(A) |
80 |
|
18 |
Painting Primer Coat of interlayer |
Interzinc 52 Intergard 475 HS |
|
19 |
Accessories: |
|
|
|
Bearing assembly temperature control |
PT-100(2pcs/bearing) |
|
|
Winding temperature control |
PT-100( 2pcs/phase) |
|
|
Space heater , V |
230 |
|
|
Number of grounding point |
2 |
|
|
For vibration detectors SPM |
3 holes( I=300mm, M8x1,25) |
|
20 |
Bearing assembly: |
|
|
|
front |
SKF (6326 C3) |
|
|
rare |
SKF (6326 C3) |
|
21 |
Weight, kg |
6800 |


An Effective Solution for Forced and Induced Draft Fans: EF High-Voltage Electric Motors in Action
Consolidated Case Study: Comprehensive Replacement of PE-Series Boiler Feed Pumps with Modern TDG Units at Power Generation Facilities of the Russian Federation
Comprehensive supply of pumping equipment for an energy facility — Novolenskaya TPP